Introduction
Capacity planning for AI usually starts with an estimate of how demand will behave. The real test comes once an application is live, and public traffic records make it possible to see how demand actually plays out. Cerbrec ran its capacity model against two public datasets, covering around 54 million AI requests, to find out what real demand looks like and what it means for building a network of data center sites.
The records, known as traces, log each request an AI service receives, minute by minute. The two datasets used here are BurstGPT, which covers 231 days of requests from one group of users of an Azure OpenAI service, and the Azure LLM Inference 2024 traces, which cover a week each of a large conversation service and a coding service.
Three Kinds of Real AI Traffic
Cerbrec’s analysis of the two datasets reveals three very different patterns of AI demand. The clearest way to compare the three is the peak-to-mean ratio, which divides demand in the busiest minute by average demand. A ratio of 2 means the busiest minute asks for twice the usual load, and the three kinds of traffic land a long way apart:
- The conversation service has a ratio of about 1.9. Its demand rises and falls through the day and seldom climbs far past twice its average, almost as if it had a ceiling.
- The coding service has a ratio of about 3.7, with occasional spells of much higher demand.
- The BurstGPT user group, sending a median of about three requests a minute, has a ratio of about 64. With so few requests in the mix, a burst of activity from a handful of users can multiply the group’s total demand.
The ratios show how high demand climbs, and the traces also reveal something less obvious: how long demand stays high once it gets there.
AI Peaks Are Not Always Spikes
Peaks in AI demand are often pictured as brief spikes lasting a minute or two, but the traces show that high demand can last much longer. Averaging each service’s demand over a full hour, in place of a single minute, puts that picture to the test. A brief spike would all but disappear in an hourly average, yet the peaks drop by only about 10 to 35%. The conversation service’s peak falls from about 1.86 times its average to about 1.62, and the coding service’s peak falls from about 3.73 to about 3.25.
This matters because high demand that arrives in busy hours and busy days is harder to manage than a brief spike. Short-term measures, such as holding requests in a brief queue, can smooth a spike that passes in a minute or two. An hour of demand above what the sites can carry is a different matter, and covering it means having the capacity installed in advance.
The length of the record also changes the peak it reveals. BurstGPT’s peak-to-mean ratio is about 18 in a typical week, about 34 in a typical month and about 64 across the full 231 days. So sizing capacity from a single week of history tends to underestimate how high demand can go.
Both findings point to the same conclusion: capacity planning has to account for the size and the duration of peaks, and the two together help explain why average utilization differs so much from one AI workload to the next.
Average Utilization Follows From the Peak
Average utilization measures the share of installed capacity a service uses over time. Because that capacity must be large enough to handle peak demand, the higher the peak relative to the average, the lower the average utilization will be when capacity is sized to that peak.
The traces make the relationship easy to see. Sizing capacity exactly to each service’s busiest minute gives an average utilization of about 54% for the conversation service, about 27% for the coding service and under 2% for the small BurstGPT user group.
The same pattern shows up across the industry. Cerbrec’s review of figures disclosed by AI providers and cloud platforms suggests that average utilization for many AI inference services sits between about 5% and 40%, and some sit at the very bottom of that range.
The traces help explain why: capacity needed during peaks sits idle during quieter periods. Reducing capacity would improve utilization but leave peak demand unmet. Sizing capacity to meet peak demand assumes that all sites are operational, leaving one more question for network design: how much extra capacity does a network need to keep serving the same peaks when one of its sites goes offline?
Headroom Is the Real Availability Lever
That extra capacity is called headroom, and it plays a central role in whether a network of Tier I sites can serve a tenant as reliably as a single Tier III building.
A Tier I site lacks the backup power and redundant infrastructure of a Tier III building, making it more vulnerable to outage. A tenant, the business renting capacity to run its AI applications, can reduce the effect of any single outage by spreading its capacity evenly across four connected Tier I sites. If one site goes offline, 75% of the total capacity remains available. The network can keep meeting demand as long as the tenant needs no more than that remaining capacity.
The conversation service illustrates how much headroom a network needs to match Tier III reliability. A four-site Tier I network sized exactly to the service’s busiest minute runs short more often than a Tier III building. Adding about 15% capacity above the peak lowers average utilization from about 54% to 47%, but allows the network to meet demand more reliably than the Tier III building.
Where a Network of Tier I Sites Stops Outperforming
Each kind of traffic in the traces has a crossover point: an average utilization above which a Tier III building is more reliable. For a four-site network, the crossover is about 47% for the conversation service and 23% for the coding service, whose higher peaks leave less room. Increasing the network from four to six sites raises these thresholds only slightly, to about 52% and 25%, respectively. Near the crossover, adding headroom is more effective than adding sites.
Many AI services run at 5% to 40% average utilization. Within this range, two to five Tier I sites can match or exceed the reliability of a single Tier III building, provided the workload can operate without overloading. At 5% to 10% utilization, two sites can outperform a Tier III building for small, spiky workloads like BurstGPT. Above about 40%, only workloads with a low peak-to-mean ratio can operate without overloading. These workloads need five or six Tier I sites, or about 15% to 20% capacity above peak demand, to match Tier III reliability.
What This Means for Tenants
The traces point to one sizing rule for tenants: a tenant’s busiest minute, measured over at least a month of history, should stay within the capacity left when one site is offline, which is three quarters of installed capacity with four sites. A tenant whose demand keeps to that rule gets service from a network of Tier I sites that is at least as good as a single Tier III building.
Cerbrec sizes each tenant’s capacity from its measured peak, so the network holds enough headroom for the way that tenant’s demand actually behaves.
Readers who want to know more can read Cerbrec’s paper, Sizing Multi-Site Capacity on Example Public Inference Traces.